01 / Direct answerChoose by required energy, verified current and installation constraints—not Ah alone.
The search question is: should you choose a 51.2V 100Ah, 200Ah or 314Ah LiFePO4 battery? In SAVYEN's published range, the three models store 5.12 kWh, 10.24 kWh and 16.076 kWh of rated energy respectively. The 100 Ah model is wall mounted, while the 200 Ah and 314 Ah models are floor-standing batteries for progressively larger energy requirements.
The 200 Ah model publishes a 200 A maximum continuous discharge current. The 314 Ah model publishes a 200 A rated charge/discharge current, which is not automatically the same engineering definition. The 100 Ah model publishes a 100 A maximum discharge current. Confirm the exact current duration, voltage range, BMS protocol, inverter settings, cables and protection for the ordered system before selecting by capacity.
100 Ah
5.12 kWh rated energy; 100 A maximum discharge; wall mounted; 435 × 153 × 700 mm; 48.5 kg.
200 Ah
10.24 kWh rated energy; 200 A maximum continuous discharge at 25 ± 3°C; floor standing; 550 × 250 × 650 mm; 89.4 kg.
314 Ah
16.076 kWh rated energy; 200 A rated charge/discharge at 25 ± 2°C; floor standing; 440 × 270 × 850 mm; 125 kg.
02 / Energy calculationConvert Ah to kWh before comparing backup time.
Nominal energy equals nominal voltage × capacity ÷ 1,000. The calculations are 51.2 × 100 ÷ 1,000 = 5.12 kWh, 51.2 × 200 ÷ 1,000 = 10.24 kWh and 51.2 × 314 ÷ 1,000 = 16.0768 kWh. The 314 Ah product page lists 16.076 kWh as its rated energy; the small difference is published rounding.
At a constant 1 kW load, rated energy ÷ load gives theoretical nameplate runtimes of about 5.12, 10.24 and 16.08 hours. Actual AC runtime is lower after the permitted operating window, inverter losses, standby consumption, wiring, temperature, ageing and reserve are included. These calculations compare nominal capacity; they are not runtime guarantees.
100 Ah to 200 Ah
The 200 Ah model has twice the rated energy at the same nominal voltage.
200 Ah to 314 Ah
The 314 Ah model has about 57% more nominal energy than the 200 Ah model.
Size from the load schedule
Add required watt-hours during the backup period, then apply confirmed usable-energy and system-efficiency values.
03 / Current and powerThe current rating must pass independently of the energy calculation.
At 51.2 V nominal, 100 A corresponds to a simple DC product of 5.12 kW and 200 A corresponds to 10.24 kW. These products are first-screen calculations, not AC inverter approvals: battery voltage changes during operation, conversion losses apply and the published current definitions and temperature conditions differ by model.
The 200 Ah page explicitly identifies 200 A as maximum continuous discharge at 25 ± 3°C. The 314 Ah page identifies 200 A as rated charge/discharge at 25 ± 2°C. Do not treat those labels as interchangeable without the supplier's complete current-duration and BMS documentation. The 100 Ah page does not publish surge duration, so no surge capability is inferred here.
First-pass formula
Estimated battery current = AC load watts ÷ (battery voltage × inverter efficiency). Use verified equipment values for final engineering.
Capacity is not power
A larger Ah rating adds energy, but it does not by itself establish continuous power, surge power or inverter compatibility.
04 / InstallationThe models differ in mounting, footprint and handling requirements.
The 100 Ah battery is a 48.5 kg wall-mounted unit. The 200 Ah battery is an 89.4 kg mobile floor-standing cabinet, and the 314 Ah battery is a 125 kg floor-standing unit. The higher-capacity models require floor loading, restraint, handling and service-clearance planning rather than a simple wall-mount substitution.
Measure the exact installation space, cable bend radius, terminal access, airflow and maintenance clearance. Confirm the enclosure protection and environmental limits for the final site; the three public pages do not support assuming identical indoor or outdoor suitability.
100 Ah wall mounted
Useful when wall structure, service access and the 435 × 153 × 700 mm enclosure are suitable.
200 Ah floor standing
A mobile cabinet format with a 550 × 250 × 650 mm published size.
314 Ah floor standing
A taller 440 × 270 × 850 mm enclosure with 125 kg published weight.
05 / Communication and expansionConfirm the exact inverter protocol and parallel design in writing.
The 100 Ah model lists RS485, CAN and Wi-Fi communication options. The 200 Ah and 314 Ah models list CAN and RS485. A shared connector name does not prove that two devices use the same CAN or RS485 protocol, message set, firmware or inverter profile.
The 200 Ah and 314 Ah product pages publish support for up to 16 units in parallel. The 100 Ah page does not publish a permitted parallel quantity, so this guide does not infer one. Even where a maximum is published, confirm matched batteries, busbars, cable lengths, overcurrent protection, current sharing, BMS addressing and the approved inverter configuration.
Protocol check
Obtain written confirmation for the exact battery model, inverter model, firmware and communication cable.
Expansion check
Confirm the ordered battery quantity, total energy, current sharing, protection and commissioning procedure.
06 / Selection checklistSend the load schedule and exact inverter model for a like-for-like proposal.
Provide the destination country, critical-load list, maximum simultaneous load, surge power and duration, required backup time, inverter or charger brand and exact model, installation dimensions, temperature range, quantity and future expansion requirement.
Ask SAVYEN to confirm usable energy, current definitions and duration, charging profile, BMS protocol, cable and protection design, environmental limits and the exact ordered configuration. Do not use a published cycle-life line as a runtime, warranty or compatibility guarantee; commercial terms and supporting documents require order-specific confirmation.
Choose 100 Ah when
5.12 kWh and the verified 100 A limit pass the project and a wall-mounted format is appropriate.
Choose 200 Ah when
10.24 kWh is required and the 200 A continuous-current, floor-space and handling checks pass.
Choose 314 Ah when
16.076 kWh is required and its separately defined 200 A rated current, larger enclosure and 125 kg mass fit the design.
SOURCESProduct data and related evidence.
Use these public sources to verify the model facts used in this guide. Final order specifications still require written confirmation.